Series CDTV Carbon Dioxide/Volatile Organic Compound Transmitters

Simultaneously Outputs Both CO2 / VOC

The Series CDTV Carbon Dioxide/Volatile Organic Compound (VOC) Transmitter reduces energy cost in buildings by lowering the amount of conditioned air based on the occupancy of the space. By sensing both CO2 and VOC, the transmitter can detect fumes that may need to be exhausted during lower occupancy periods.

Product Applications

  • HVAC applications in hospitals, schools, and commercial buildings
  • Demand control ventilation
  • Odor control
  • Waiting rooms or other spaces that may be occupied 24 hours a day

Models & Ordering

Shipping Information

All shipping times are dependent on product availability at time of shipment.

Although we make every effort to ensure a continuous supply of our products, occasional circumstances may force us to temporarily run out of a product, or have shipping delays. Should this occur, customers will be notified soon after placement of any orders for such products and, if applicable, items will be put on backorder. For orders requiring expedited shipment, our customer service team can be contacted to confirm product availability

Build Your Custom Part. Use our Product Configurator

Model Description Usually Ships* Price Order
CDTV-2N404
Ships: 1-2 Weeks
Price: $394.00
Wall Voc & CO2 transmitter, universal analog outputs, 2000 ppm CO2 1-2 Weeks* $394.00 Order
CDTV-2N404-LCD
Ships: 1-2 Weeks
Price: $434.75
Wall Voc & CO2 transmitter, universal analog outputs, 2000 ppm CO2 with LCD display 1-2 Weeks* $434.75 Order
CDTV-2N4A4
Ships: 1-2 Weeks
Price: $400.10
Wall Voc & CO2 transmitter, universal analog outputs, 2000 ppm CO2, 10K Ohm Type III temperature sensor 1-2 Weeks* $400.10 Order
CDTV-2N4A4-LCD
Ships: 1-2 Weeks
Price: $440.85
Wall Voc & CO2 transmitter, universal analog outputs, 2000 ppm CO2, 10K Ohm Type III temperature sensor with LCD display 1-2 Weeks* $440.85 Order
CDTV-2N4B4
Ships: 1-2 Weeks
Price: $400.10
Wall Voc & CO2 transmitter, universal analog outputs, 2000 ppm CO2, 10K Ohm Type II temperature sensor 1-2 Weeks* $400.10 Order
CDTV-2N4B4-LCD
Ships: 1-2 Weeks
Price: $440.85
Wall Voc & CO2 transmitter, universal analog outputs, 2000 ppm CO2, 10K Ohm Type II temperature sensor with LCD display 1-2 Weeks* $440.85 Order

Can't find what you need? Build Your Custom Part. Use our Product Configurator

Specifications

Range:
CO2: 0 to 2000 or 0 to 5000 ppm (depending on model); VOC: 0 to 2000 ppm CO2 equivalent.
Accuracy:
CO2: ±40 ppm ±3% of reading.
Temperature Dependence:
±8 ppm / °C at 1100 ppm.
Non-Linearity:
CO2: 16 ppm.
Pressure Dependence:
CO2: 0.13% of reading per mm of Hg.
Response Time:
CO2: 2 minutes for 99% step change; VOC: 5 minutes.
Temperature Limits:
32 to 122°F (0 to 50°C).
Duct Air Velocity Range:
0-4000 FPM (20.32 m/s).
Power Requirements:
16 to 35 VDC / 19 to 28 VAC.
Power Consumption:
Average: 2 watts; Peak: 3.75 watts.
Sensor:
CO2: Single-beam, dual-wavelength NDIR; VOC: MEMS metal oxide semiconductor.
Output:
Current: 0 to 20 mA, 4 to 20 mA, 0 to 10 mA, or 2 to 10 mA (depending on selection jumper, max 500 O); Voltage: 0 to 10 VDC, 2 to 10 VDC, 0 to 5 VDC, or 1 to 5 VDC (depending on selection jumper, min 500 O); Relay: SPST NO 2A @ 30 VDC.
Weight:
5.6 oz (158.8 g).
Enclosure Rating:
Duct mount: NEMA 4X (IP66) for housing only; Wall mount: IP20.
Agency Approvals:
CE.

Features

  • Combination VOC and CO2 outputs reduce labor and material costs
  • Single beam dual wavelength NDIR CO2 sensor allows for use in spaces that may be occupied 24 hours a day
  • VOC output is correlated to be equivalent to CO2 measurements
  • Ventilate using ASHRE’s occupancy-based VRP Algorithm

Accessories

Model Number Description Usually Ships* Price Order
Remote display with mini USB display. A-449 Remote display with mini USB display. Next Day $65.00 Order
Remote display with push buttons and mini USB. (Necessary for models with –NBC option) A-449A Remote display with push buttons and mini USB. (Necessary for models with –NBC option) Less Than 1 Week $130.00 Order
Gas Calibration Kit <br><b>(GROUND SHIPMENTS ONLY)</b> GCK-200CO-2000CO2 Gas Calibration Kit
(GROUND SHIPMENTS ONLY)
Call for Details $688.00 Order
Accessory kit including terminal block and power supply. A-CDT-KIT Accessory kit including terminal block and power supply. 1-2 Weeks $51.00 Order

Videos

Model Chart

EXAMPLE CDTV 2 D 4 0 4 RLY Series CDTV-2D404-RLY, Carbon Dioxide VOC Transmitter, gas concentration range 2000 ppm, duct mount, carbon dioxide output 0-5 VDC/0-10VDC/4-20mA, relay output
SERIES CDTV             Carbon Dioxide VOC Transmitter
GAS CONCENTRATION RANGE   2
5
          2000 ppm
5000 ppm
MOUNTING CONFIGURATION     D
N
        Duct Mount
North American Style Wall Mount
CARBON DIOXIDE OUTPUT       4       0-5 VDC/0-10 VDC/4-20mA
TEMPERATURE OUTPUT         0
A
B
C
D
E
F
    NONE                       
10K Ohm Type 3 NTC Thermistor
10K Ohm Type 2 NTC Thermistor
3K Ohm NTC Thermistor
PT100 Ohm RTD               
PT1000 Ohm RTD              
20K Ohm NTC Thermistor
VOC OUTPUT           4   0-5 VDC/0-10 VDC/4-20 mA
OPTIONS             COC
FC
LCD
RLY
Certificate of Calibration
Factory Calibration Certificate
LCD Display (not available with Duct Mount)
Relay Output

Product Literature

Manuals

Catalog Pages

Product Data Sheet

SlideShare

Approvals

Photo Downloads

You must be logged in to view this content.
Click here to login to your account.

Product Reviews

Only registered users can write reviews. Please Sign in or create an account